Sale!
Home / Eaton / Final Sale Eaton S3M100KX – S3M100KX

Final Sale Eaton S3M100KX – S3M100KX

Original price was: $22,366.80.Current price is: $8,946.72.

For orders under $60.00, a shipping fee of $9.99 applies.
Fast delivery, satisfaction guaranteed.
Secure Payment.
SKU: SK0033581 Category:
Share

Battery Backup and VFI Operation Protect Critical LoadsThe SmartOnline® S3M100KX IGBT UPS supports the continuous availability of your most important loads through all power conditions, providing a compact backup power platform that’s easy to manage and inexpensive to operate. Sophisticated voltage and frequency independent (VFI) operation and advanced IGBT rectifier technology with DSP control deliver reliable output power quality. Providing up to 100kVA of clean, continuous power, this 3-phase UPS system is perfect for critical applications in IT, communications, corporate, commercial, retail, financial, security, transportation, emergency and light industrial environments.Best-in-Class Footprint for Easy Integration into Your Network ApplicationThis on-line double-conversion UPS system has a very small footprint of just 0.54 square meters. It requires less valuable space in your data center, and you can install the UPS system in spaces that would previously have required expensive retrofitting.Efficient Operation and Design Reduces Cost of OwnershipThis IGBT UPS benefits from highly efficient transformer-free double-conversion technology that delivers operating cost savings. It achieves 94% efficiency in double-conversion mode and up to 98% in ECO mode, reducing your power and cooling costs. A low THDi (<3%) improves generator compatibility. A low THDv (?2%) and active power factor correction improve output performance. The hardware and firmware platform design reduces the number of unique boards, improving mean time to repair (MTTR) and resulting in reduced downtime. Built-in static and maintenance bypass transfer UPS load to utility power during faults, overloads and maintenance, which also avoids costly system downtime.External Batteries Supply Reliable Backup with Expandable Runtime OptionsThe S3M100KX uses external scalable battery cabinets, such as BP480V65 and BP480V100 (sold separately), to provide up to three hours of backup support in case of a power failure. Add the optional TEMPC100200 thermostat kit to enable temperature-compensated charging for optimized battery lifespan. The UPS system automatically restarts after a lengthy power outage.Intuitive Color Touchscreen Display Delivers Important Performance Information at a GlanceThe large (25.4 cm/10 inches) front-panel color interface enables comprehensive local monitoring and control capability. It displays critical operating conditions and diagnostic data, such as phase load levels, available runtime, alarm status, battery charge, and voltage and frequency values. Six LEDs indicate bypass, on-line, inverter, battery and alarm/fault modes.Optional WEBCARDLX Network Interface Offers 24/7 Remote Access for Monitoring and ControlThe optional WEBCARDLX (sold separately) with the latest version of PowerAlert Device Manager firmware (PADM20) provides enhanced remote management capabilities, including customizable dashboard graphs to fit user preferences. The PADM20 upgrade and PowerAlert Element Manager (PAEM) software form a powerful tool for expanding maintenance functions in large installations, including firmware update checks and backup and restoration of device configurations. Auto Probe allows a UPS with switched loads to automatically reboot devices if a network communication failure is detected. This preserves uptime and minimizes the time and expense associated with on-site support.Parallel Capability Provides Additional Capacity and Redundancy up to 2 UnitsConnect two S3M100KX units in parallel using separate/shared battery cabinets for increased capacity.

  • S3M100KX SmartOnline S3MX Series 3-Phase 380/400/415V 100kVA 90kW On-Line Double-Conversion UPS
  • P100200KIT parallel cable kit
  • RS-232 cable
  • Owner’s manual
OVERVIEW
UPC Code 037332225429
UPS Type On-Line
INPUT
Input Phase 3-Phase
Rated input current (Maximum Load) 165A
Nominal Input Voltage(s) Supported 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye
Nominal Input Voltage Description 3-Phase Wye, 4 wire plus ground (L1, L2, L3, N, G)
UPS Input Connection Type Hardwire
Input Circuit Breakers 200A (3 pole)
Power Factor (Input)   .99PF (100% load)
THDi   <3% (100% load)
OUTPUT
Output Capacity (VA) 100000
Output Capacity (kVA) 100
Output Capacity (Watts) 90000
Output Capacity (kW) 90.00
Output Capacity Details Supports up to 100% load continuously in double conversion mode; Supports up to 110% load for 60 minutes, up to to 125% load for 10 minutes, up to 150% load for 1min and greater than 150% for 1 milliseconds before switching to bypass mode; Inverter mode is automatically restored as load levels are reduced to 70% or less;Configuration options support up to 2 S3M100KX systems wired in parallel for increased capacity or fault-tolerant, redundant operation
Power Factor   0,9
Crest Factor   3:1
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details Automatic frequency selection
Output Voltage Regulation (Line Mode) +/- 1%
Output Voltage Regulation (Economy Line Mode) +/-15V of nominal
Output Voltage Regulation (Battery Mode) +/- 1%
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
Nominal Output Voltage(s) Supported 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye
Output Receptacles Hardwire
Individually Controllable Load Banks   Yes
BATTERY
Expandable Runtime Yes
External Battery Pack Compatibility   BP480V100;  BP480V100-NIB ; BP480V40;  BP480V40-NIB ; BP480V65
DC System Voltage (VDC) +/- 240
Battery Recharge Rate (Included Batteries) 9 hours to 90% (Internal batteries)
VOLTAGE REGULATION
Voltage Regulation Description Online, double-conversion power conditioning maintains output within 1% of the selected nominal voltage in online mode
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Large (25.4cm/10 in) color touchscreen display enables comprehensive local monitoring, diagnostics and control through an advanced, intuitive and user-friendly interface. The display has six sub-screens: HOME, CONTROL, MEASUREMENTS, SETUP, INFORMATION and EVENT. Each of these screens is intuitive and comprehensive providing specifics from input and output phase loads, voltages, frequencies, battery charge status, system operating mode (online, standby, ECO, Battery, fault) status, specific measurement in every operating mode, current and event history of up to 500 events to enable diagnostics and system fault troubleshooting. It is powerful local management tool at your fingertips.
Audible Alarm Alarms warn users of a variety of operational conditions: There are audible alarms for all modes of operation, as well as fault modes. Please refer to the owner’s manual for a full list of audible alarms. Here are a few: Bypass Mode (beeps every 1 min), Battery Mode (beeps every 2 seconds), Low Battery Mode (beeps every 0.5 seconds), UPS Fault Mode (beeps continuously), and UPS alarm (beeps every 1 seconds).
LED Indicators 6 LEDs report BYPASS / LINE / INV/ BATTERY / FAULT/ALARM modes
PHYSICAL
Primary Form Factor Tower
Cooling Method Fans
Installation Form Factors Supported with Included Accessories Tower
Primary UPS Depth (mm) 945
Primary UPS Height (mm) 1,015
Primary UPS Width (mm) 567
Shipping Dimensions (hwd / cm) 118.11 x 70.61 x 112.52
Shipping Weight (kg) 223.50
UPS Housing Material Steel
UPS Power Module Dimensions (Height x Width x Depth, mm) 1015 x 567 x 945
UPS Power Module Dimensions (hwd, cm) 101.50 x 56.69 x 94.49
UPS Power Module Weight (kg) 197.00
ENVIRONMENTAL
Operating Temperature Range 32° to 104°F (0° to 40°C)
Storage Temperature Range 5° to 140°F (-15° to 60°C) without battery
Relative Humidity 5 to 95%, non-condensing
Operating Elevation (ft.) < 3280ft (Capacity de-rates by 1% for every 328ft over 3280ft )
Audible Noise <70dBA at 1meter
Operating Elevation (m) < 1000m (Capacity de-rates by 1% for every 100m over 1000m)
COMMUNICATIONS
Network Management Cards WEBCARDLX;  WEBCARDLXE ;  MODBUSCARDSV ; RELAYCARDSV
Network Monitoring Port Description Card accessory slot supports network management interface WEBCARDLX card or a programmable I/O relay RELAYCARDSV card options
Communications Cable DB9/RS-232 cable included
Communications Interface DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
LINE / BATTERY TRANSFER
Transfer Time   Zero transfer time Online to Battery, Inverter to Bypass 0ms (Synchronous), and Inverter to ECO mode < 20ms.
Low Voltage Transfer to Battery Power (Setpoint) 120V(Ph-N), 208V (Ph-Ph)@ 50% load/176V (Ph-N), 305V (Ph-Ph)@ 100% load.
High Voltage Transfer to Battery Power (Setpoint) 276 (Ph-N), 478V (Ph-Ph) @ 50% or 100% load.
FEATURES & SPECIFICATIONS
Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported
High Availability UPS Features   Automatic inverter bypass; Manual bypass switch; Auto Probe Monitoring (requires WEBCARDLXE); Zero transfer time; On-Line/Double-Conversion
Green Energy-Saving Features High efficiency economy mode operation
Grounding Details Yes
APPLICATIONS
UPS Applications Mission Critical Applications
STANDARDS & COMPLIANCE
Product Certifications IEC/EN 62040
Product Compliance RoHS; CE (Europe); UKCA
WARRANTY & SUPPORT
Product Warranty Period (International) 2-year limited warranty
3-Phase Warranty Statement Tripp Lite 3-Phase UPS Factory Warranty